System bus (CAN) for Lenze PLC devices
Configuration (FIF interface)
5−10
l
PLC−Systembus EN 2.0
5.10.3 Response in the case of system bus fault messages
Overview of the system bus error sources registered by the PLC as well as of the possible settings
for the corresponding response:
Fault message Possible settings/response
Display Error
No.
Meaning TRIP Message Warning Fault/QS
P
Off Code
CE11 122 Communication error FIF−CAN1_IN
(Time monitoring can be set via C2457/1)
ü ü C2481
CE12 123 Communication error FIF−CAN2_IN
(Time monitoring can be set via C2457/2)
ü ü C2482
CE13 124 Communication error FIF−CAN3_IN
(Time monitoring can be set via C2457/3)
ü ü C2483
CE14 125 BUS−OFF state
(too many faulty telegrams were received)
ü ü C2484
Lenze setting
ü Possible
− Not possible