49
3.2.2.2. Initiate
The initiate service is used for the logic initiation between two
participants. The controller returns the following parameters:
Value Meaning
Profile-Number:
21
hex
DRIVECOM profile of version 1
When using the automation
module:
0 No profile
Password:
0 The password function of PROFIBUS
is not supported
Access Groups:
0 No access groups
Access Protection Supported:
TRUE Access protection is supported
Version OV
Value: 0
3.2.2.3. Abort
The abort service is used to abort a logic communication.
3.2.2.4. Status
This service supplies status information about the controller.
The following parameters are returned by the controller:
Status Value Meaning
Logical
Status
0 ready to communicate
(L-C001 = 5)
1 limited number of services
(L-C001 <> 5)
Information about the momentary
operating state (Lenze parameter
L-C001) of the controller concerning
communication.
Physical
Status
0 ready for operation
controller state
"OPERATION
ENABLED"
1 partially operational, all
other possible controller
states
Information about the momentary
operating state of the controller.
Please refer to controller states in
figure 5.
Local
Detail
Parameter "status word" 24-bit value, which contains the profile
parameter "status word" (index
6041
hex
) in the bits 0 to 15.
Bits 16 to 23 are set to 0.
3.2.2.5. Get-OV
Listing of object description for every parameter and data type.
Vista de página 50