Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 14
Product description
Features and variants
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.2 Features and variants
The EtherNet/IP Communication Unit is available in the following versions:
The EtherNet/IP Communication Unit is ...
mounted on top of the Wiring Unit (E84DGVNxx);
supplied internally via the Drive Unit (E84DGDVxxxxxxxx) or externally via a separate
voltage source.
The I/O connections can be brought into the device via M12 connectors or cable glands.
Devices without an integrated safety system (safety option) have no analog input and no relay
output.
The integrated safety system can be used on machines for the protection of persons.
The Inverter Drive 8400 motec is always an adapter device:
EtherNet/IP adapter with "Level 2" functionality
2-port interface with integrated switch functionality
Access to all Lenze parameters (configurable via TCP/IP using the Lenze »Engineer«)
Up to 3 TCP/IP socket connections for communication with the Lenze »Engineer«
Support of "IP Config Pending" (activation of changed IP configuration by "power off/on" or
"type 0 reset")
Support of the redundancy protocol DLR (Device Level Ring) as "beacon-based ring node"
Up to 10 input data words to the scanner (20 bytes)
Up to 8 output data words from the scanner (16 bytes)
Further CIP features:
Max. 8 CIP connections
1 "exclusive owner" connection
I/O connection type: cyclic
•Minimum I/O cycle time: 4 ms
Support of multicast messages, UCMM, ACD, BOOTP/DHCP, VLAN tagging/DSCP
Product series Type designation Product features
Enclosure
IP 65
EtherNet/IP
M12
I/O: Terminal
I/O: M12
Safety
Inverter Drives 8400 motec
EtherNet/IP Communication Unit
E84DGFCGANP 
E84DGFCG9NP 
E84DGFCGAJP 
E84DGFCG9JP  
Hardware manual for Inverter Drives 8400 motec
Here you will find detailed information on the integrated safety system (safety option).
Software manual / »Engineer« online help for the Inverter Drive 8400 motec
Here you will find detailed information on how to configure the safety system (safety
option).
Vista de página 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 148 149

Comentários a estes Manuais

Sem comentários