9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter response to a read error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Response identification Axis
(mirrored)
Number of indices
0xXX 0x81 0x00 0x01
Parameter has not been read
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without
additional information
Byte 7 Byte 8
Error code
High byte Low byte
For the meaning, see the "Error codes" ( 70) chapter