6 13433283_P94MI01D_EN
Technical Data
2.2 Connections and I/O
2.2.1 P1 - Input Power (Mains) Connection
Standard Models
1
2
3
4
L3
L2
L1
PE
Doubler Models
1
2
3
4
L2/N
L1
N
PE
Pin Name Function Name Function
1 PE Protective Earth (Ground) PE Protective Earth (Ground)
2 L1 AC Power in N AC Power Neutral (120V Doubler only)
3 L2 AC Power in L1 AC Power in
4 L3 AC Power in (3~ models only) L2/N AC Power in (non-doubler operation)
Fuse PE L1, L2, L3
EN 60204 UL
Type
[A]
1~/3~
[A]
1~/3~
[A]
1~/3~
[mm
2
]
[AWG]
[mm]
[in]
[Nm]
[lb-in]
[mm
2
]
[AWG]
1~/3~
[mm]
[in]
[Nm]
[lb-in]
E94_020S1N_~ M20/M10 C20/C10 20/10
2.5
14
6
0.25
0.5
4.5
2.5/2.5
14/14
6
0.25
0.5
4.5
E94_040S1N_~ M32/M20 C32/C20 30/20
4
12
4/2.5
12/14
E94_020S2F_~ M20 C20 20
2.5
14
6
0.25
0.5
4.5
2.5
14
6
0.25
0.5
4.5
E94_040S2F_~ M20 C20 20
E94_080S2F_~ M32 C32 32
4
12
4
12
E94_100S2F_~ M40 C40 40
6
10
6
10
E94_020Y2N_~ M20/M16 C20/C16 20/15
2.5
14
6
0.25
0.5
4.5
2.5/2.5
14/14
6
0.25
0.5
4.5
E94_040Y2N_~ M20/M16 C20/C16 20/15
E94_080Y2N_~ M32/M20 C32/C20 30/20
4
12
4/2.5
12/14
E94_100Y2N_~ M32/M20 C32/C20 30/20
6
10
6/2.5
10/14
0.79
7
E94_120Y2N_~ M50/M32 C50/C32 50/30
6
10
6/4
10/12
0.5
4.5
E94_180T2N_~ M40 C40 40
6
10
0.79
7
6
10
0.79
7
E94_020T4N_~ M10 C10 10
2.5
14
6
0.25
0.5
4.5
2.5
14
6
0.25
0.5
4.5
E94_040T4N_~ M10 C10 10
E94_060T4N_~ M20 C20 20
E94_090T4N_~ M25 C25 25
1) Installations with high fault current due to large supply mains may require a type D circuit breaker.
2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.
3) Thermal-magnetic type breakers preferred.
WARNING!
The PositionServo drive runs on phase-to-phase voltage. For the standard drive, either a delta or wye transformer may be used for
3-phase input. However, for reinforced insulation of user accessible I/O circuits, each phase voltage to ground must be less than or
equal to 300VAC rms. This means that the power system must use center grounded wye secondary configuration for 400/480VAC
mains.
STOP!
For the E94 _020S1N_~ and E94_040S1N_~ doubler models, do NOT apply 240VAC to the N and L1 terminals. Severe damage to
the drive will result.
1) 2)
3)