Lenze EVF9383−EV Manual do Utilizador Página 3

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 41
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 2
Key for overview
Position Description
9300 vector frequency inverter − master
9300 vector frequency inverter − slave
Connections and interfaces
Position Description
L1, L2, L3, PE Mains connection
+UG, −UG DC supply (only for the variants V210, V240, V270, V300)
BR1, BR2 Connection of brake resistor (only for the variants V210, V240, V270, V300)
U, V, W, PE Motor connection
X1 AIF interface (automation interface)
slot for communication module (e.g. keypad XT EMZ9371BC)
X3 Jumper for setting the analog input signal at X6/1, X6/2
X4 Terminal strip for connection of system bus (CAN)
X5 Terminal strips for connection of digital inputs and outputs
X6 Terminal strips for connection of analog inputs and outputs
X8 Sub−D connector (male) for connection of incremental encoder with TTL level or sin/cos encoder and KTY ther-
mal sensor of the motor
X9 Sub−D connector (male) for connection of digital frequency input signal
X10 Sub−D connector (female) for connection of digital frequency output signal
X11 Terminal strip for connection of relay output K
SR
for "safe standstill"
Status displays
Position LED red LED green Operating status
Off On Controller is enabled
On On Mains is switched on and automatic start is inhibited
Off Blinking slowly Controller is inhibited
Off On Motor data identification is active
Blinking quickly Off Undervoltage or overvoltage
Blinking slowly Off Active fault