9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Cyclic synchronous torque mode (IEC 61800-7)
164 L EDS94TA11010xxxx EN 1.2 - 03/2010
3.14.6 Control commands & status information
The CiA402 (0x6040
) control word serves to execute control commands in the "cyclic
synchronous torque mode":
The CiA402 (0x6041
) status word serves to output the following status information in the
" cyclic synchronous torque mode":
Control word Status Function
Bit 4 0 Reserved (bit must be set to "0")
Bit 5 0 Reserved (bit must be set to "0")
Bit 6 0 Reserved (bit must be set to "0")
Bit 8 0 Ê 1Stop
Status word Status Meaning
Bit 12 0 "Cyclic synchronous torque mode" is not active
1 "Cyclic synchronous torque mode" is active