Electrical installation
Wiring
6
EDK82ZAFSC DE/EN/FR 5.0
39
H2_verdrahtung−INS_Klemmenbeleg
X3/ Signal
type
Function
(Lenze setting: bold print)
Level
(Lenze setting: bold print)
62 Analog
output
Output frequency 0  +6 V
0  +10 V
1)
7 GND1, Reference potential for analog signals
8 Analog
input
Input for actual value or setpoint
Switch over the range with the DIP switch and in C0034:
l Voltage signal
0  +5 V
0  +10 V
−10  +10 V
2)
l Current signal
0  +20 mA
+4  +20 mA
+4  +20 mA (open−circuit
monitored)
9 Internal, stabilised DC voltage source for the
setpoint potentiometer
+5.2 V
20 Internal DC voltage supply for control of digital
inputs and outputs
+20 V ±10 % (ref.: X3/7)
28
Digital
inputs
Controller inhibit (CINH) 1 = enable
E1
3)
Activation of JOG frequencies
JOG1 = 20 Hz
JOG2 = 30 Hz
JOG3 = 40 Hz
e1 E2
JOG1 1 0
E2
3)
JOG2 0 1
JOG3 1 1
E3 DC−injection brake (DCB) 1 = DCB
E4 Change of direction of rotation
CW/CCW rotation
E4
CW 0
CCW 1
39 GND2, Reference potential for digital signals
A1 Digital
output
Ready for operation
l internal supply:
l external supply:
0  +20 V
0  +24 V
59 DC supply for X3/A1
l internal (bridge to X3/20):
l external:
+20 V
+24 V
1)
Output level 0  +10 V: Adapt offset (C0109/C0422) and gain (C0108/C0420)
2)
Adjust offset (C0026) and gain (C0027) separately for each function module ...
− after replacing the function module or the basic device.
− after loading the Lenze setting.
3)
Frequency input alternatively 0  10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425