Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013 13
Product description
Features and variants
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.2 Features and variants
The AS-Interface Communication Unit is available in the following versions:
The AS-Interface Communication Unit is ...
mounted on top of the Wiring Unit (E84DGVNxx);
supplied internally by the Drive Unit (E84DGDVxxxxxxxx) and externally by the AS-i bus.
The I/O connections can be brought into the device via M12 connectors or cable glands.
Devices without an integrated safety system (safety option) have no analog input and no relay
output.
The integrated safety system can be used on machines for the protection of persons.
The Communication Unit AS-Interface supports the services of the AS-i version 3.0:
cyclic reading and writing of single parameters
•cyclic drive control
acyclic reading and writing of parameter sets
acyclic query of diagnostic data
Two AS-i slaves are contained in the Communication Unit. Thus, two AS-i addresses are
assigned. AS-i concept of the Communication Unit
( 33)
The acyclic communication via the AS-i bus and the slave 2 are available for the read and write
access to parameters.
The AS-i slaves can be addressed ...
via a programming unit or from the master or
by means of parameters (e.g. via »Engineer«, keypad or EPM).
Up to 31 standard slaves can be connected to an AS-i network. In this case the max. cycle time
is 5 ms. Up to 62 so-called A/B slaves can be connected if extended addressing is used. In this
case the max. cycle time is 10 ms.
Synchronisation
( 32) of input and output data is possible.
Communication with the Lenze »Engineer« (access to all Lenze parameters) is executed via the
diagnostic interface of the Drive Unit.
Product series Type designation Product features
Enclosure
IP 65
AS-Interface
M12
I/O: Terminal
I/O: M12
Safety
Inverter Drives 8400 motec
Communication Unit AS-Interface
E84DGFCAANP 
E84DGFCA9NP 
E84DGFCAAJP 
E84DGFCA9JP  
"Inverter Drives 8400 motec" hardware manual
Here you will find detailed information on the integrated safety system (safety option).
Software manual / »Engineer« online help "Inverter Drives 8400 motec"
Here you will find detailed information on how to configure the safety system (safety
option).