4 Electrical installation
Wiring to a host
EDKMF2133 DE/EN/FR 6.1
46
H1_E_INST−Inst_2133−2
4 Electrical installation
Wiring to a host
Danger!
Additional electrical isolation must be installed if
ƒ an 820X and 821X controller is connected to the host and
ƒ reliable electrical isolation (reinforced insulation) in accordance with
EN61800−5−1 is needed.
The connection of the PROFIBUS bus system is shown in the survey drawing.
333
1
222
0m
1200 m
GG + 2133 GG + 2133 GG + 2133
E82ZAFP005
Fig. 1 Example: PROFIBUS with RS485 wiring (without repeater)
No. Element Note
1 Host e.g. PC or PLC with PROFIBUS master interface module
2 Bus cable Adapt baud rate to bus cable length
3 PROFIBUS slave Controller (see 40) which can be used with the EMF2133IB
communication module