Electrical installation
Important notes
5
22
BA 33.0003 EN 1.0
5 Electrical installation
5.1 Important notes
Danger!
Hazardous voltage at the power terminals, even if the plug is removed:
residual voltage > 60 V!
Before working at the power terminals, disconnect the drive controller from
the mains and w ait until the m otor stands still (voltage at the contact while
the motor is turning).
General
z
Observe the notes in the terminal box of the motor.
z
Firmly tighten all connections.
z
Connect PE connector to earthing screw.
z
Fit connecting cable with strain relief.
z
Carefully earth the motor.
Voltage
supply
Servo spindle
motors
z
Servo spindle motors must be fed by servo inverters.
z
Connect the integrated encoder at the motor side with the
corresponding connections of the servo inverter.
Holding brake
(optional)
z
DC supply according to nameplate data of the brake or supply with AC
voltage via upstream rectifier (only spring-operated brake, PM brakes
205 V)
1)
z
Brakes for 205 V can be fed from the 230 V mains via bridge rectifiers,
brakes for 103 V from the 115 V mains.
z
Do not supply brakes with half-wave rectifiers from the AC system.
Inverter
operation
z
Observe the connection notes in the corresponding operating
instructions.
z
Ensure that motor and inverter are correctly assigned.
z
In particular, observe the speed limits and winding load. *
Cable cross
sections
z
Correctly dimension the connecting cables to avoid impermissible
heating.
z
Maintain minimum cross sections to DIN 57100 and secure
appropriately ( see Tab. 1).
Motor
protection
Protection against
overload
z
Common current-dependent motor protection switches for average
operating frequency
Set to rated current as indicated on the nameplate.
z
With very high operating frequency: Use three-phase AC motors from
Lenze with thermal switches or PTC thermistors in the winding.
The thermal switches are integrated in the winding as NO contact or
NC contact. The response temperature is permanently set.
Motor supply cable
z
No protection possible via overtemperature protector switches or PTC
thermistors of the motor winding
Take measures according to DIN 57100 / VDE 0530.
Inverter operation
z
The current or voltage conversion can increase the output current
significantly above the input current.
The motor supply cable cannot be fused via the mains input fuses o f
the inverter. Take measures according to DIN 57100 / VDE 0530.
1) Supply PM brakes for 24 VDC only with smooth DC v oltage (ripple 1%)
* Voltage limits: 1.5 kV peak value, 5 kV/µs r ate of rise; additional information: see the data sheet.