L DMS 4.0 EN - 07/2007 39
L-force Loader
Appendix
Error numbers, causes & remedies
Error while downloading L-force 9400 application
8000C702h Controller inhibit has not been set. Set controller inhibit on the target system.
8000C704h Application has not been stopped. Stop the application on the target system.
8000C801h Error message of target system while
downloading.
Restart target system to establish the "ready
for download" state.
8000C807h Error message of target system:
Licence level does not correspond.
Create the application again using the
Engineer and transfer it to the target system
or update the target system.
8000C808h Error message of target system:
Target does not correspond.
8000C809h Error message of target system:
Error while configuring the module.
8000C80Ah
8000C8xxh Other (not yet listed) error messages of the
target system while downloading.
Create the application again using the
Engineer and transfer it to the target system.
Errors within the DriveServer
E7C18000h Error during download preparations. Repeat download.
E7C18001h PLC has not been stopped. Stop the PLC program on the target system.
E7C18002h Controller inhibit has not been set. Set controller inhibit on the target system.
E7C18003h Incorrect file type (no LC9 file). Create new LC9 file.
E7C18004h Checksum test is negative (incorrect
checksum).
Repeat download.
Increase time-out time in the system bus
configurator (e.g. to 3 seconds).
E7C18005h Item can momentarily not be accessed due to
download.
Repeat download after a few minutes or
restart your PC.
E7C18006h Target system is momentarily busy copying
RAM blocks.
Start the PLC program on the target system.
E7C18007h Error occurred after the download. Repeat download.
E7C18008h Error after version comparison during
download of an LC7 file.
• Different versions in LC7 file and target
system.
Update the operating system for 9300 EK.
E7C18009h "Cam" template is not available on the target
system.
Create DDS project based on Cam template
and transfer it into the target system.
Error number Cause Remedy