Installation
4-5
BA2131EN
Wiring features:
Features:
Communication medium RS485
Network topology without repeater: line
withrepeater: line or tree
Possible number of controllers without repeater: 32
withrepeater: 127
Maximum cable length 1200 m (depending on the baud rate and the cable type used)
Maximum baudrate 9.6-12000 kbit/s
The connection of the bus system PROFIBUS-DP is shown in the survey drawing. The required
accessories (e.g. connection cables) are listed in chapter 8.1.
1
93XX
82XX
2
3
8200 vector
Fig. 4-3 PROFIBUS with RS485 wiring (without repeater)
1Host
2 Bus-connector (
4-6)
3Buscable(
4-6)
Wiring
Warning!
If the 2131 fieldbus module is no longer supplied with voltage, the bus system will continue
operation. However, the connected controller can no longer be accessed from the host.
If single bus participants are to be disconnected, it must be ensured that the bus terminators
at the physical cable ends remain active.
Only use cables which correspond to the listed specifications (see chapter 8.1).
Observe the bus connector drawing. ( 4-6)
Connect the controller using the bus connector.
Note: The bus system will not be interrupted if the bus connector is pulled off the controller.
Connect a bus terminator to the physical bus ends. The bus terminator is integrated into the
bus connector and can be activated via a switch.
Observe the wiring notes and the documentation for the control system.