Technical data
3-2
L
_^ONMObk
3.3 Rated data
2102IB.V001
2102IB.V002 2102IB.V003
Communication media RS232 (LECOM-A)
RS485 (LECOM-B)
RS485 (LECOM-B) Optical fibre
(LECOM-LI)
Current consumption 80 mA 60 mA 70 mA
External supply
(terminals 39/59)
V=24VDC
V
RMS
=15TO30VDC;W=5%
V
RMS
=20TO25VDC;W=48%;V
SS
< 35 V
2102IB.V001 / 2102IB.V002 / 2102IB.V003:
Rated insulation voltage Type of insulation
to PE 50 V AC no electrical isolation
for external supply (terminals 39/59) - no electrical isolation
for power stage
820X / 821X 270 V AC basic insulation
822X / 8200 vector 270 V AC double basic insulation
93XX 270 V AC double basic insulation
Insulation voltages
f
o
r
b
u
t
e
m
for control terminals
for bus systems
820X / 8200 vector
(with internal supply)
- no electrical isolation
8200 vector
(with external supply)
100 V AC basic insulation
821X 50 V AC electrical isolation
822X 270 V AC basic insulation
93XX 270 V AC basic insulation
for external bus systems 50 V AC electrical isolation
Degree of pollution VDE 0110 part 2 pollution degree 2
3.4 Dimensions
Fig. 3-1 Dimensions of the 2102 fieldbus module (all dimensions in mm)