Lenze DDS Function library Drive Manual do Utilizador Página 93

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 103
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 92
Function library LenzeDrive.lib
Special functions
2.7.6 Right/Left/Quickstop (L_RLQ)
2−83
L
LenzeDrive.lib EN 1.7
2.7.6 Right/Left/Quickstop (L_RLQ)
This FB links the input for the direction of rotation and the QSP function, and is safe against an open
circuit.
bCw_b
L_RLQ
bQSP_b
bCwCCw_b
bCCw_b
Fig. 2−79 Right/Left/Quickstop (L_RLQ)
VariableName DataType SignalType VariableType Note
bCw_b Bool binary VAR_INPUT Right
bCCw_b Bool binary VAR_INPUT Left
bCwCCw_b Bool binary VAR_OUTPUT Status Right/Left
bQSP_b Bool binary VAR_OUTPUT Set Quickstop
Function
After mains connection and simultaneous TRUE at both inputs, the outputs are set as
follows:
Inputs Outputs
bCw_b bCCw_b bCwCCw_b bQSP_b
1 1 0 1
0 = FALSE
1 = TRUE
The following truth−table results only if the inputs were set to TRUE once after power
switch−on
Inputs Outputs
bCw_b bCCw_b bCwCCw_b bQSP_b
0 0 0 1
1 0 1 0
0 1 1 0
1 1 unchanged unchanged
0 = FALSE
1 = TRUE
If you set both inputs to TRUE during operation, both outputs still have their previous output value.
Vista de página 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 102 103

Comentários a estes Manuais

Sem comentários