Sicherheitshinweise
Sicherheitshinweise für die Installation nach UL oder UR
2
l
11
EDK94ARN24 DE/EN/FR/ES/IT 2.1
2.3 Sicherheitshinweise für die Installation nach U
L
oder U
R
J Warnings!
ƒ Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V max.
ƒ Voltage of the fuses must at least be suitable with the input voltage of the
drive. Branch circuit short circuit protection with fuses in accordance to
UL248.
ƒ Maximum surrounding air temperature: 55 °C.
ƒ Use 60 °C copper wire only for power circuits.
ƒ Use 75 °C copper wire only for 24 V DC control circuits of filter, except for
other control circuits.
Branch circuit protection
Type Fuse [A]
E94ARNE0134 30
E94ARNE0244 60