Parameter setting
6-3
BA2112EN
6.1.1.3 Process-data assignment for 8200 vector
Digitaland analog input and output signal can be configured freely (see Operating Instructions “8200
vector”: Codes C0410, C0412, C0417 and C0421).
The change of the code C0001 to 3 starts the preconfiguration of the process data words in the
controller (see chapter 5.3,
( 5-2) ).
Structure of the PO-data response (data to drive)
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6
Control word
High byte
Control word
Low byte
AIF-IN.W1
High byte
AIF-IN.W1
Low byte
AIF-IN.W2
High byte
AIF-IN.W2
Low byte
Control word: see chapter 6.1.3.2.
AIF-IN.Wx see C0412.
Structure of the PI data response (data from drive)
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6
Status word
High byte
Status word
Low byte
AIF-OUT.W1
High byte
AIF-OUT.W1
Low byte
AIF-OUT.W2
High byte
AIF-OUT.W2
Low byte
Status word: see chapter 6.1.3.3.
AIF-OUT.Wx see C0421.
Tip!
• Frequency and speed are normalized with á24000 á480 Hz.
• Torque is normalized with 16384 100%.