Function library
Function blocks
3.2.3 Function block CDATA
3−33
l
EDSVS9332K−EXT EN 4.0
3.2.3.11 Stretching, compression, offset of the Y axis
) Note!
This operating mode only works with digital frequency preselection (chapter 3.2.3.3),
i.e. CDATA−DFIN must be selected with C1332 = 0.
Stretching / compression
The code C1319 serves to set the mode for stretching or compression. Two modes are used for
differentiation:
C1319 Mode
Result if input CDATA−XFACT =
100 % −100 % >100% <100%
0
DFIN @XFACT
100%
No stretching,
no compression
No stretching,
no compression,
reversal of direction
(profile is processed in
backward direction)
Compression Stretching
1
DFIN @ 100%
XFACT
See TIP below Stretching Compression
) Note!
l Values < 1% are internally limited to +1% at input XFACT via C1319=1
(compression).
l If you do not want a stretching or compression, connect CDATA−XFACT to
FIXED100% (Lenze setting).
Offset
Use input CDATA−XOFFS to shift the X position by a constant value.
( Stop!
The drive follows this position change with the max. possible torque! This is why
l CDATA−XOFFS should be changed while the drive is in a latch phase or
l a ramp function generator (e.g. RFGPHx) should be used.