21 RG-MCMOD
Drive Control & Communication
6.2 Parameter List
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name Range of Adjustment
Modbus value (decimal value)
Factory Default
51 (33) 0 LINE VOLTS 00 - High
01 - Low
02 - Auto
02 - Auto
52 (34) 1 SPEED #1 Min. Freq - Max. Freq (0.00 - 120.00 Hz) 2000 (20.00 Hz)
5
53 (35) 2 SPEED #2 Min. Freq - Max. Freq 2000 (20.00 Hz)
5
54 (36) 3 SPEED #3 Min. Freq - Max. Freq 2000 (20.00 Hz)
5
55 (37) 4 SPEED #4 Min. Freq - Max. Freq 2000 (20.00 Hz)
5
56 (38) 5 SKIP #1 MC1: 0 - 65000 (.00 - 650.00 Hz)
MC3: 0 - Max Freq (.00 Hz - Max. Freq)
0 (.00 Hz)
5
57 (39) 6 SKIP #2 MC1: 0 - 65000 (.00 - 650.00 Hz);
MC3: .0 - Max Freq (00 Hz - Max. Freq)
0 (.00 Hz)
5
58 (3A) 7 BAND WID 0 - 1000 (.00 - 10.00 Hz) 100 (1.00 Hz)
5
59 (3B) 8 ACCEL Refer to Note 4 300 (30.0 sec)
60 (3C) 9 DECEL Refer to Note 5 300 (30.0 sec)
61 (3D) 10 MIN FREQ 0 - Max Frequency (0.00 - 120.00 Hz) 50 (.50 Hz)
5
62 (3E) 11 MAX FREQ Min Frequency - 12000 (120.00 Hz) Note 6 6000 (60.00 Hz)
5
63 (3F) 12 DC BRAKE Refer to Note 7 0 (.0 VDC)
64 (40) 13 DC TIME 0 - 9999 (.0 - 999.9 sec) 0 (.0 sec)
65 (41) 14 DYN BRAKE 00 - Off
01 - On
00 - Off
67 (43) 16 CURRENT 25 - 180 (25 - 180%), Refer to Note 8 180 (180%)
68 (44) 17 MOTOR OL 25 - 100 (25 - 100%) 100 (100%)
69 (45) 18 BASE 2000 - 36000 (20.00 - 360.0 Hz) 6000 (60.00 Hz)
5
70 (46) 19 FX BOOST 0 - 300 (0.0 - 30.0%) Refer to Note 9
71 (47) 20
2,3
AC BOOST 0 - 200 (0.0 - 20.0%) 0 (.0%)
72 (48) 21
2,3
SLIP CMP 0 - 50 (0.0 - 5.0%) 0 (.0%)
73 (49) 22 TORQUE 00 - Contant
01 - Variable
02 - CT/NOCMP
00 - Constant
74 (4A) 23 CARRIER 00 - 2.5 kHz
01 - 6 kHz
02 - 8 kHz
03 - 10 kHz
04 - 12 kHz
05 - 14 kHz
00 - 2.5 kHz