13435744_EDBMH01_v13 13
5 MCH RATINGS
The three tables in this section provide the input and output ratings of the MCH Series
drive. The tables are divided by Series Number: MH200, MH400 and MH500.
NOTE
The output current ratings are based on operation at carrier
frequencies of 8kHz and below.
At full ambient temperature, operation at carrier frequencies above
8 kHz require derating the drive by multiplying the output current
rating by the following factors: 0.94 at 10kHz, 0.89 at 12kHz, and
0.83 at 14kHz.
For more information, refer to Parameter 23 - CARRIER FREQ in
Section 18 - DESCRIPTION OF PARAMETERS.
MH200 SERIES RATINGS
MODEL
INPUT OUTPUT
(200/240 Vac, 50 - 60 Hz) (0 - 200/230 Vac)
MODEL FOR MOTORS NOMINAL NOMINAL
NUMBER RATED INPUT CURRENT POWER CURRENT POWER
(NOTE 1) HP kW PHASE (AMPS) (KVA) (AMPS) (KVA)
MH210 1 0.75 3 5.5 / 4.8 2.0 4.6 / 4.0 1.6
MH220 2 1.5 3 9.3 / 8.1 3.4 7.8 / 6.8 2.7
MH230 3 2.2 3 13.0 / 11.3 4.7 11.0 / 9.6 3.8
MH250 5 3.7 3 20 / 17.7 7.4 17.5 / 15.2 6.1
MH275 7.5 5.5 3 30 / 26 10.6 25 / 22 8.8
MH2100 10 7.5 3 37 / 32 13.2 32 / 28 11.2
MH2150 15 11 3 55 / 48 19.8 48 / 42 16.7
MH2200 20 15 3 70 / 61 25.3 62 / 54 21.5
MH2250 25 18.5 3 89 / 77 32.0 78 / 68 27.1
MH2300 30 22 3 104 / 90 37.6 92 / 80 31.9
MH2400
3
40 30 3 99 / 99 41.0 104 / 104 41.4
MH2500
3
50 37.5 3 122 / 122 50.7 130 / 130 51.8
MH2600
3
60 45 3 145 / 145 60.5 154 / 154 61.3
NOTE 1: Refer to Section 3.0 for model number breakdown.
NOTE 2: Refer to Section 8.0 for recommended fuse type.
NOTE 3: For branch circuit protection, the 40HP, 50HP and 60HP 230V models must only
be installed with the appropriately rated UL Listed fuses.