15.3 REMOTE H/O/A
Shown below is the wiring diagram for selecting H/O/A from the terminal strip. Also
shown is the wiring for a 0-10 VDC or 4-20 mA speed reference signal. In HAND mode,
TB-1 must be closed to TB-2 in order to start the drive. In AUTO mode, close TB-1 to
TB-2 to RUN, and open to STOP.
RUN / STOP
CIRCUIT COMMON
0-10 VDC INPUT
4-20 mA INPUT
1 2 5A 5B 6
10A 12A RXA TXB10B 2 13A 13B
13C
13D 14
15 2
16 17 18
FORM C
RELAY
CIRCUIT COMMON
MAINTAINED
RUN/STOP CONTACT
(AUTO MODE ONLY)
The TB-2 terminals are internally tied together
AUTO MODE SELECT
HAND MODE SELECT
CIRCUIT COMMON
HAND
OFF
AUTO
HAND
OFF
AUTO
NOTES:
1. Program TB-13C (Parameter 49) to HAND. This forces TB-12A to act as AUTO.
2. In AUTO mode (TB-12A closed to TB-2), close TB-1 to TB-2 to RUN, and open to
STOP. The speed reference will be determined by AUTO SOURCE (Parameter
24).
3. When HAND mode is selected (TB-13C closed to TB-2), TB-1 must also be
closed to TB-2 in order to RUN. The speed reference will be determined by HAND
SOURCE (Parameter 29).