Lenze MCH Series Manual do Utilizador Página 40

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 39
36 13435744_EDBMH01_v13
15 MCH CONTROL WIRING DIAGRAMS
The following wiring diagrams apply to standard MCH drives. Refer to Appendix A for
control wiring for the Bypass option, or Appendix B for control wiring for the Option Box.
15.1 MCH TERMINAL STRIP
Shown below is the terminal strip on the main control board, along with a brief description
of the function of each terminal.
RUN / STOP
CIRCUIT COMMON
0-10 VDC SPEED REFERENCE INPUT
10 VDC SUPPLY FOR SPEED POT
0-10 OR 2-10 VDC OUTPUT: FREQUENCY
0-10 OR 2-10 VDC OUTPUT: LOAD
CIRCUIT COMMON
AUTO MODE SELECT
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13C FUNCTION SELECT
TB-13D FUNCTION SELECT
OPEN-COLLECTOR OUTPUT
OPEN-COLLECTOR OUTPUT
RS-485 SERIAL
COMMUNICATIONS
CIRCUIT COMMON
4-20 mA SPEED REFERENCE INPUT
1 2 5A 5B 6
10A 12A RXA TXB10B 2 13A 13B
13C
13D 14
15 2
16 17 18
FORM C
RELAY
The TB-2 terminals are internally tied together
NOTE: The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB-13C, TB-
13D, TB-14, TB-15, TB-16 and TB-18 are dependent on the programming
of certain parameters. In most cases, the name of the parameter matches
the number of the terminal, allowing quick and easy programming of the
terminals to suit the application. The exception is TB-16 and TB-18, which
are governed by Parameter 54 - RELAY.
A complete description of operating the drive in the AUTO mode can be found in Section
14.2. The following diagrams provide a quick reference to wire the drive for the most
common congurations.