Electrical installation
Wiring of system bus (CAN)
4
103
EDKCSEE040 DE/EN/FR 4.0
Assignment of the plug connectors
X4 (CAN) X14 (CAN-AUX) Description
CH CAH CAN-HIGH
CL CAL CAN-LOW
CG CAG Reference potential
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898-2:
CAN cable in accordance with ISO 11898-2
Cable type Paired with shielding
Impedance 120 (95 ... 140 )
Cable resistance/cross-section
Cable length 300 m 70 m/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m 40 m/m / 0.5 mm
2
(AWG20)
Signal propagation delay 5ns/m