Electrical installation
Power terminals
Connection to the DC bus (+U
G
,-U
G
)
4
87
EDKCSEE040 DE/EN/FR 4.0
4.3.2 Connection to the DC bus (+U
G
,-U
G
)
Stop!
ƒ The supply of Lenze controllers of the 82xx and 93xx series is not
permitted.
ƒ If synchronous motors with a high centrifugal mass are used, a
considerable amount of energy can be fed back into the DC bus.
Please take this into account when dimensioning the brake
resistor.
ƒ If the total cable length is > 20 m, install an axis module or a capacitor
module directly at the power supply module.
ƒ Design the ±U
G
cables twisted and as short as possible. Ensure
short-circuit-proof routing!
ƒ Cable length (module module) > 30 cm: install shielded ±U
G
cables.
Documentation of the ECSxS/P/M/A axis modules
Observe the enclosed notes.
Documentation of the ECSxK capacitor module
Observe the enclosed notes.