Lenze ECSEExxx Manual do Utilizador Página 88

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 164
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 87
Electrical installation
Power terminals
Connection to the DC bus (+U
G
,-U
G
)
4
88
EDKCSEE040 DE/EN/FR 4.0
Fuses
Fusing the DC-bus interconnection is not required if power supply modules of
the ECS series are used which are fused on the mains side.
Cable cross-section
Cable
length
(module/
module)
Wire end ferrule Cable
cross-section
Tightening torque Stripping length
Up to 20 m
Without wire end
ferrule
6mm
2
(AWG 10)
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb-in)
5mmforscrew
connection
10 mm for spring
connection
With insulated wire
end ferrule
>20m
Without wire end
ferrule
10 mm
2
(AWG 8)
With insulated wire
end ferrule
Use pin-end
connectors for
wiring!
Vista de página 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 163 164

Comentários a estes Manuais

Sem comentários