Drive PLC Developer Studio
Appendix
15-13
l DDS EN 2.3
No. Possible remedyCause
3501 No address in VAR_CONFIG for <Name> Insert an address for the named variable in the global variable list with
Variable_Configuration. Ressourcen
WGlobal_Variables ^ 8-2
3502 Wrong data type of <Name> in VAR_CONFIG The named variable was declared in the global variable list (with Variable configuration) with
a different data type than in the function block.
3503 Wrong address type of <Name> in VAR_CONFIG The named variable was declared in the global variable list (with Variable configuration) with
a different address type than in the function block.
3504 Initial values for VAR_CONFIG variables are not s upported A Variable Configuration variable has been declared with address and initial value. However,
an initial value can be defined only for input variables without address assignment.
3505 <Name> is no valid instance path A non-existent variable was specified in the variable configuration.
3506 Access path expected A correct access path is missing for one variable in the global variable list for access
variables:
<Identifier>:’<Access path>’:<T ype> <Access type>
3507 No address specification permitted for V AR_ACCESS An address assignment exists for one variable in t he global variable list f or access variables.
Correct definition:
<Identifier>:’<Access path>’:<T ype> <Access type>
3550 The task name <Name> was used twice You have defined two tasks with the same name.
Rename one of them.
3551 The task <Name> must contain at least one program call Insert a program call, or delete the task.
3552 Event variable <Name> in task <Name> not defined You have used an event variable in the configuration of the named task, that is not globally
declared in the project.
Use a different variable or define the entered variable globally.
3553 Event variable <Name> in task <Name> must be
BOOL-type
UseaBOOL-typevariableaseventvariable.
3554 Task entr y <Name> must be a program or a global
function block instance.
You have entered a function or an undefined organization block in the field Program call.
3555 The task entry <Name> is parameterized incorrectly You have specified parameters in the field Program call that do not correspond to the
declaration of the organization block.
3600 Implicit variable not found. First use the command Compile all. Contact the control manufacturer if the error message
reappears.
3601 <Name> is a reserved variable name. You have declared a variable in the project that is already reserved for the code generator.
Rename this variable.
3610 <Name> not supported The named feature is not supported by this version.
3611 The compile directory <Name> is incorrect. You have entered an incorrect directory for the compile files in the ProjectWOptions
Category Directories.
3612 Maximum number of organization units (<Number>)
exceeded! Compile will be aborted.
You are using too many organization units and data types in the project.
Change the maximum number of organization units in dialog box Automation system settings
tab Memory layout.
Note!
The tab memory layout cannot be edited at the moment.
3613 Compile t erminated The user terminated the compile.
3614 The project contains no organization unit <Name> (entry
function) or task configuration
A project requires a Program-type entry function (e.g. PLC_PRG) or a task configuration.
3615 <Name> (entry function) must be Program-type. You are using an entr y function (e. g. PLC_PRG) other than Program-type.
3616 Programs in external libraries are not supported The library to be saved contains a program that will not be available during library use.
3617 Insufficient memory Increase the virtual memor y capacity of your processor.
3618 The current code generator does not support bit access The code generator for the currently set automation system does not support bit access to
variables.
3700 An organization unit named <Name> already exists in
library <Name>
You are using an organization unit name that has already been assigned for a library
organization unit. Rename the organization unit.
3701 The organization unit name in the declaration name does
not match the name in the object list.
Rename your organization unit using the menu commands ProjectWRename object or
change the name of the organization unit in its declaration part. The name must appear
directly after the keywords Program, Function or Function block.
3702 Too many identifiers A maximum of 100 identifiers may be specified per variable declaration.
3703 Several declarations with the same identifier <name> Several identically named identifiers exist in the object’s declaration part.
3705 Data recursion: <Organization unit 0> à
<Organization unit 1> à ... à <Organization unit 0>
An FB instance was used that requires itself to function.
3720 AT must be followed by an address. Insert a valid address after the keyword AT or change the keyword AT.
3721 Only V AR and V AR_GLOBAL can be assigned to addresses. Copy the declaration to a VAR or VAR_GLOBAL section.
3722 Only simple Boolean variables may be located at the
specified address.
Change the address or the variable type stated in the declaration.
3722 Only simple Boolean variables may be located at the
specified address.
Change the address or the variable type stated in the declaration.
3728 PL C_PRG(): Impermissible address %IX141.58.0. Specify a correct address.