Lenze E84Dxxxxx Manual do Utilizador Página 43

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 70
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 42
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05 43
5 Safety option 30
5.1 Safe inputs
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Short overview of "Safe inputs" parameter group:
Sensor type/sensor function
Sensor type and function can be parameterised.
Tip!
Detailed information on sensor inputs, active and passive sensors can be found in the
manual for the drive-based safety system.
Free assignment
If "Free assignment" has been selected as sensor function, the safety function selected via this
parameter is assigned to the safe input. The following safety functions can be selected:
Safe torque off (STO) ( 29)
Safe stop 1 (SS1)
( 30)
Discrepancy time
Maximum time for which both channels of a safe input may have non-equivalent states without
the safety engineering detecting an error.
Input delay
Time between the recognition of the signal change and the effective evaluation of an input signal.
As a result, multiple and short signal changes due to contact bounce of the components are not
taken into account.
Parameter Information Lenze setting
Value Unit
C15030/1...2 SD-In1...2 sensor type Input is deactivated
C15031/1...2
SD-In1...2 sensor function Free assignment
C15032/1...2
SD-In1...2 free assignment STO
C15033/1...2 SD-In1...2 discrepancy time 10 ms
C15034/1...2
SD-In1...2 input delay 0 ms
Note!
If an error (e.g. a discrepancy error) occurs at a safe input to which the "operation mode
selector" sensor function is assigned, then normal operation (corresponding to the OFF
state) is selected.
The LED "S_Error" is blinking, no STO
is tripped.
Special operation can only be selected again if the error has been eliminated and
acknowledged.
Note!
If "No function" has been selected, no safety function is assigned to the safe input.
Function test and monitoring of the discrepancy time remain active and the status of
the input is transmitted to the control via the safety bus (if parameterised).