Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17 36
6 Commissioning
6.2 Node address setting
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2 Node address setting
The POWERLINK node address (node ID) is set via the front DIP switches.
[6-1] DIP switch
The labelling on the housing corresponds to the valencies of the individual DIP switches for
determining the node address (Node ID).
Lenze setting for DIP switches 1 ... 128 = OFF (invalid value "0")
Valid addresses in the POWERLINK network for the communication module:
240: Managing Node
The Managing Node mode" supports max. 50 nodes.
1 … 100: Controlled Node with Lenze module E94AYCEP as Managing Node
1 … 239: Controlled Node with Managing Node of another manufacturer
The corresponding Ethernet IP address of the communication module results from the address
setting of the DIP switches:
IP address: 192.168.100.[Node ID]
Note!
Each network node address must only be used once.
The node address setting in the configuration software (e.g. »Engineer«) and the DIP
switches must be identical for each node.
Switch the voltage supply of the communication module off and on again to activate
changed settings.