Commissioning
Possible settings with the front switch
7
Feldbus-Baugruppe 2113 INTERBUS
7.5
7.5.2
L
7.5-3
EDSIBS-1.0-06/2003
ON
OFF
OPEN
12345678
PCP
Length
2113IBU005
PCP S5 S6 Maximum number of process
data words (PD)
ID code
0 OFF OFF 10 3
hex
1 OFF ON 9 E3
hex
2 ON OFF 8 E0
hex
4 ON ON 6 E1
hex
)
))
) Note!
Impermissible settings are indicated by the yellow bus LED
(communication)
( 7.4-1).
Display of the current switch position S5/S6 for number of
parameter data words (PCP) is possible because of code L-1917.
ON
OFF
OPEN
1234567 8
Drivecom
2113IBU005
S7 Explanation
OFF with AIF-CTRL control
ON with DRIVECOM control
)
))
) Note!
Display of the current switch position S7 is possible because of
code L-C1916.
ON
OFF
OPEN
12345678
Baud
2113IBU005
S8 Baud rate Maximum cable length between neighboring participants
OFF 500 kBit/s 400 m
ON 2MBit/s 150 m
)
))
) Note!
The baud rate can only be set through switch S8.
Setting number of parameter
data words (PCP)31
Select AIF-CTRL or DRIVECOM
control32
Select baud rate33