Data transfer
Process data preconfiguration depending on L-C0009
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.3
L
7.6-25
EDSIBS-1.0-06/2003
Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures 1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 14 (e.g. via keypad)
2
.
S
e
t
L
C
0
0
0
9
1
4
(
e
.
g
.
v
i
a
k
e
y
p
a
d
)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
Result The indexes 6000
hex
and 6001
hex
accept the configurations DCSTW
and DCG.
The process data length (PD) is set to 2 words by L- C1910 = 4.
DRIVECOM is activated with L-C1911 = 1.
Acceptance of settings The fieldbus module must be switched on again to activate the process
data word length.
Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures 1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 25 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
Result The indexes 6000
hex
and 6001
hex
accept the configurations GSTW,
AIF-W1, A IF-W2.
The process data length (PD) is set to 3 words by L- C1910 = 6.
DRIVECOM is activated by L-C1911 = 0.
Acceptance of settings The fieldbus module must be switched on again to activate the process
data word length.
Example 3: DRIVECOM control with 5 process data words (e.g. configuration L-C0009 = 21)
Settings/measures 1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 21 (e.g. via keypad)
3. DIP switch
S1 = OFF, S2 = ON, S3 = OFF, S4 = ON (PD = 5 words)
S5/S6: Set required PCP data word length
S7 = ON (DRIVECOM activated)
4. Attach the fieldbus module again and connect it to the voltage
supply
Result The indexes 6000
hex
and 6001
hex
accept the configurations DCSTW,
DCG, AIF-W2, AIF-W3, AIF-W4.
Codes L-C1910 = 6 and L-C1911 = 1 are written, but ar e not active
(DIP switch in position “ON”).
Acceptance of settings A process data word length of 5 words and DRIVECOM are immediately
active through switches.
Example 4: Configuration of 10 PD words to AIF interface (configuration L-C0009 = 27).
Settings/measures 1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 27 (e.g. via keypad)
3. DIP switch
S1 = ON, S2 = OFF, S3 = ON, S4 = OFF (PD = 10 words)
S5 = OFF, S6 = OFF: no PCP
S7 = OFF (DRIVECOM deactivated)
4. Attach the fieldbus module again and connect it to the voltage
supply
Result The indexes 6000
hex
and 6001
hex
accept the configurations
AIF-W1 .... AIF-W10.
Codes L-C1910 = 6 and L-C1911 = 1 are written, but ar e not active
(DIP switch in position “ON”).
Acceptance of settings All switch settings become active immediately.
Examples for process data