3.6 Code table
9300 Servo PLC
Appendix
3−140
L
9300 Servo PLC EN 5.1
Code InformationPossible settingsLCDCode Information
SelectionLenze
LCD
C0545 PH offset 0 Digital frequency output DFOUT_IO_DigitalFrequency:
Phase offset of the zero pulse for incremental encoder
simulation (1 rev. = 65535 inc.)
0 {1 inc} 65535
C0547 DFOUT_nOut_v
g
Digital frequency output DFOUT_IO_DigitalFrequency:
DFOUT_nOut_v as analog value (if C0540 = 0)
−199.99 {0.01 %} 199.99
C0549 DFOUT_nOut_v
g
Digital frequency output DFOUT_IO_DigitalFrequency:
DFOUT_nOut_v as speed value (if C0540 = 1)
−32767 {1 rpm} 32767
C0559 SD8 filter t 1.00 Filter time constant (SD8)
1 {1 ms} 200 Example:
When the setting is "10 ms", an SD8 TRIP is initiated after
10 ms.
C0575 max fld weak 4.00 Factor for limiting the max. possible field weakening
Setting "4.00" means, for example, max. 400 % field
weakening possible.
1.00 {0.01} 8.00
C0576 nErr Window 100 Tolerance margin for speed monitoring
Referred to n
max
.
100 % = lowest monitoring sensitivity.
0 {1 %} 100
C0577 Vp fld weak 3.00 Field weakening controller gain V
p
0.00 {0.01 ms} 15.99
C0578 Tn fld weak 10.0 Field weakening controller reset time Tn
2.0 {0.5 ms} 8192.0
8000 ms = switched off
C0579 MONIT nErr 3 Speed monitoring configuration
0 TRIP
1 Message
2 Warning
3 Off
4 FAIL−QSP
C0580 MONIT SD8 3 Monitoring configuration: Sin/cos encoder
0 TRIP
3 Off
Setting of the filter time constant (SD8) via C0559
C0581 MONIT Eer 0 Monitoring configuration: External error
0 TRIP
1 Message
2 Warning
3 Off
C0582 MONIT OH4 2 Monitoring configuration: Heatsink temperature
(Heatsink temperature > limit temperature C0122)
2 Warning
3 Off
C0583 MONIT OH3 Monitoring configuration: Motor temperature
(Motor temperature > fixed limit temperature)
Dependent on C0086
0 TRIP
3 Off
C0584 MONIT OH7 Monitoring configuration: Motor temperature
(Motor temperature > variable limit temperature C0121)
Dependent on C0086
Temperature monitoring via resolver input
2 Warning
3 Off