2.6 ANALOG2_IO (node number 12)
9300 Servo PLC
System blocks
2−28
L
9300 Servo PLC EN 5.1
2.6 ANALOG2_IO (node number 12)
2.6.1 Inputs_ANALOG2 (analog input)
The input is the interface for differential analog signals between terminals X6/3, 4.
AIN2_nIn_a
Inputs_ANALOG2
C0405
X6
Fig. 2−11 Inputs_ANALOG2
System variables
Variable Data type Signal type Address Display
code
Display
format
Note
AIN2_nIn_a Integer Analog %IW12.0 C0405 dec [%] Analog input 2
Terminal assignment
Terminal Use Measuring range
X6/3, 4 Differential input for master voltage
(no effect of jumper X3)
Level:
Resolution:
Scaling:
−10 V ... +10 V
5 mV (11 bits + sign)
10 V 16384 100 %
2.6.2 Outputs_ANALOG2 (analog output)
The output can be used as a monitor output. Internal analog signals can be output as voltage signals
via terminal X6/63 and used, for instance, as display values or setpoints for slave drives.
Outputs_ANALOG2
AOUT2_nOut_a
C0439
63
X6
Fig. 2−12 Outputs_ANALOG2
System variables
Variable Data type Signal type Address Display
code
Display
format
Note
AOUT2_nOut_a Integer Analog %QW12.0 C0439 dec [%] Analog output 2
Terminal assignment
Terminal Use Measuring range
X6/63 Analog output 2 (monitor 2) Level:
Resolution:
Scaling:
−10 V ... +10 V (max. 2 mA)
20 mV (9 bits + sign)
10 V 16384 100 %
X6/7 Internal ground, GND −