Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-11
EDSIBS-1.0-06/2003
7.6.2.2 Process data signals for 8200 vector frequency inverters
The function block AIF (AIF=automation interface) is the data interface between
the 8200 vector and the fieldbus module. The function block consists of AIF-OUT
and AIF-IN.
ThefollowingparameterscanbeassignedtothePI-data:
Index Subindex Name Explanation Lenze setting:
Index 6000
hex
see
6041 0 DRIVECOM status word PI data word 1 ^ 7.6-39
6044 0 DRIVECOM speed Actual speed [rpm] PI data word 2 ^ 7.6-42
6054 0 DRIVECOM actual
percentage value
Actual speed [%]
100% = 16383
^ 7.6-43
5F69 0 Device status word
(L-C0150)
Table below
1 AIF-OUT.W1 AIF word 1
5
5
2 AIF-OUT.W2 AIF word 2 PI data word 3
AIF-OUT.Wx is parameterised under code L-C0421.
Process data telegram from
drive