Diagnostics
Troubleshooting and fault elimination
Controller is inhibited
9
l
113
EDSMF2133IB EN 5.0
9.2 Troubleshooting and fault elimination
9.2.1 Controller is inhibited
The controller cannot be enabled via PROFIBUS process data, i.e. the status "OPERATION
ENABLED" is not reached.
PROFIBUS
initialisation
OK?
Check
PROFIBUS
Check 2133
communication
module
Is the yellow
LED (bus) blinking?
82XX / 8200 vector:
Set the operating mode (C0001) to
3 (save parameters (C0003) if
necessary)
PIW1 =
xxxx xxxx x100 0000
bin
(switch−on inhibit)?
PIW1 =
xxxx xxxx 0xxx 1000
bin
(fault)?
Reset
fault (TRIP)
1
Select POW1 = 0000
hex
No
Yes
No
Yes
Yes