2.12 MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−72
L
9300 Servo PLC EN 5.0
2.12.17.7 LP1 − monitoring of the motor phases
This monitoring function checks if a motor phase has failed.
Note!
This monitoring function can only be used for asynchronous motors.
When this monitoring function is activated, the calculating time available for the user is
reduced.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x032 LP1 Motor phase failure MCTRL_bMotorphaseFail_b
Lenze setting
Setting possible
The monitoring limit is set under C0599.
The response is set under C0597.
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0597 MONIT LP1
3 Configuration of motor phase
monitoring (LP1)
0 TRIP
2 Warning
3 Off
C0599 Limit LP1
5 LP1 fault monitoring limit
0.01 {0.01 %} 10.00
Error acknowledgement
1. Check motor cables.
2. Execute TRIP−RESET.