Control technology | EtherCAT communication manual
Parameter reference
Interface parameters of the MC-ETC communication card in slot 1
170 L DMS 3.1 EN 01/2011 TD17
C1082/1
C1082/2
C1082/3
C1086/2
C1086/3
C1086/4
Parameter | Name:
C1082/1 | ECAT Distributed Clocks State
Data type: BITFIELD_3
Index: 23493.1
d
=
0x5BC5.0x01
h
Display of the state of the distributed clocks
The bits are set to the value 1 when the respective states are reached.
Value is bit-coded:
Bit 0 DC: Activated
Bit 1 DC: Synchronised
Bit 2 DC: Busy
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1082/2 | ECAT DC Slave Sync Deviation Limit
Data type: UNSIGNED_32
Index: 23493.2
d
=
0x5BC5.0x02
h
Permitted deviation of the distributed clocks of all devices in nanoseconds. If the permitted deviation is exceeded,
the master initiates a resynchronisation of the distributed clocks.
Display range (min. value | unit | max. value)
0 ns 4294967295
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1082/3 | ECAT DC Current Deviation
Data type: INTEGER_32
Index: 23493.3
d
=
0x5BC5.0x03
h
Current maximum deviation of the distributed clocks of all devices in nanoseconds.
Display range (min. value | unit | max. value)
0 ns 2147483647
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/2 | ECAT Configuration Checksum CRC-32
Data type: UNSIGNED_32
Index: 23489.2
d
=
0x5BC1.0x02
h
Checksum of the master configuration file (loaded from stack/active). The stack determines the checksum of the
loaded/active master configuration file. If this file does not exist, the value "0x00000000" is displayed.
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/3 | ECAT Number of found Slaves
Data type: UNSIGNED_32
Index: 23489.3
d
=
0x5BC1.0x03
h
Number of slaves connected to the fieldbus
Display range (min. value | unit | max. value)
0 4294967295
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/4 | ECAT Number of found DC-Slaves
Data type: UNSIGNED_32
Index: 23489.4
d
=
0x5BC1.0x04
h
Number of slaves connected to the fieldbus supporting distributed clocks
Display range (min. value | unit | max. value)
0 4294967295
; Read access Write access CINH PLC STOP No transfer