Control technology | EtherCAT communication manual
Parameter reference
Interface parameters of the MC-ETC communication card in slot 2
184 L DMS 3.1 EN 01/2011 TD17
C1581/1
C1581/2
C1581/3
Parameter | Name:
C1581/1 | ECAT State Change Command
Data type: UNSIGNED_32
Index: 22994.1
d
=
0x59D2.0x01
h
This code can be used to change the master state.
Note: The parameter should only be set to analyse start problems (e.g. master/bus does not reach the Operational
state). Setting this parameter only sets the state of the master stack. All other nodes remain in their previous states.
Changing the master state via this code may result in an unstable system state.
A higher bus state than the one initiated by the PLC can never be reached.
A reload of the master configuration cannot be initiated.
Loading the PLC program normally stops the bus and sets it to the Pre-Operational state. If this is not possible,
the bus remains in the Unknown or Initialisation state.
Starting the PLC program normally sets the bus to the Operational state. If this is not possible, the bus remains
in the Pre-Operational or Safe Operational state.
Selection list (Lenze setting printed in bold)
0No Operation
1Init
2 Pre-Operational
4 Safe-Operational
8Operational
; Read access ; Write access CINH PLC STOP ; No transfer
Parameter | Name:
C1581/2 | ECAT Master State
Data type: UNSIGNED_8
Index: 22994.2
d
=
0x59D2.0x02
h
Display of the current master state
Selection list(read only)
0 Unknown
1 Init
2 Pre-Operational
3 Bootstrap Mode Bootstrap Mode is not supported.
4 Safe-Operational
8 Operational
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1581/3 | ECAT Master in requested Mode
Data type: UNSIGNED_8
Index: 22994.3
d
=
0x59D2.0x03
h
The state is usually requested by the PLC. For possible requested states see C1581/1 ( 184).
Value "0": Master is not in the requested state.
Value "1": Master is in the requested state.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer