Control technology | EtherCAT communication manual
Commissioning of the system
Detailed commissioning steps
78 L DMS 3.1 EN 01/2011 TD17
7.2.8.6 Loading the control configuration onto the IPC
How to load the control configuration onto the IPC:
1. Select the OnlineWrite file to PLC menu command.
2. Select the required file from the Write file to PLC dialog box.
3. Confirm the selection by clicking the Open button.
The file is loaded onto the IPC and saved there under the same name.
Tip!
The OnlineRead file from PLC menu command can be used to reload a file from
the IPC onto the »PLC Designer« project.