12 Diagnostics
12.6 System error messages
188
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
0x98110106 ETC_E_SOE_ERRORCODE_BUFFER_FULL The Rx memory buffer is full (EtherCAT call with too little data buffer).
Is not supported.
0x98110107 ETC_E_SOE_ERRORCODE_NO_DATA No data state
Is not supported.
0x98110108 ETC_E_SOE_ERRORCODE_NO_DEFAULT_VALUE No standard value
Is not supported.
0x98110109 ETC_E_SOE_ERRORCODE_DEFAULT_LONG The standard value transmission is too long.
Is not supported.
0x9811010a ETC_E_SOE_ERRORCODE_DEFAULT_WP The standard value cannot be changed (read only).
Is not supported.
0x9811010b ETC_E_SOE_ERRORCODE_INVL_DRIVE_NO Invalid drive number
Is not supported.
0x9811010c ETC_E_SOE_ERRORCODE_GENERAL_ERROR General error
Is not supported.
0x9811010d ETC_E_SOE_ERRCODE_NO_ELEM_ADR No element has been addressed.
Is not supported.
0x9811010e ETC_E_SLAVE_NOT_PRESENT The slave is not available at the fieldbus.
0x9811010f ETC_E_NO_FOE_SUPPORT_BS The FoE protocol is not supported in the bootstrap state.
0x98110110 ETC_E_EEPROMRELOADERROR Command error during EEPROM reload
0x98110111 ETC_E_SLAVECTRLRESETERROR Command error during slave controller reset
0x98110112 ETC_E_SYSDRIVERMISSING The system driver ect.sys could not be opened.
Internal error. Please contact Lenze.
0x9811011E ETC_E_BUSCONFIG_TOPOCHANGE The fieldbus configuration could not be detected. The bus topology has been
changed.
0x9811011F ETC_E_EOE_MBX_WKC_ERROR Error at EoE mailbox reception: Working counter
0x98110120 ETC_E_FOE_MBX_WKC_ERROR Error at FoE mailbox reception: Working counter
0x98110121 ETC_E_SOE_MBX_WKC_ERROR Error at SoE mailbox reception: Working counter
Is not supported.
0x98110122 ETC_E_AOE_MBX_WKC_ERROR Error at AoE mailbox reception: Working counter
Is not supported.
0x98110123 ETC_E_VOE_MBX_WKC_ERROR Error at VoE mailbox reception: Working counter
Is not supported.
0x98110124 ETC_E_EEPROMASSIGNERROR The EEPROM assignment has failed.
Internal error. Please contact Lenze.
0x98110125 ETC_E_MBX_ERROR_TYPE Error at mailbox reception
Internal error. Please contact Lenze.
0x981201C1 ETC_DCM_E_NOTINITIALIZED The initialisation has not been successful. The initialisation function has not
been called.
Internal error. Please contact Lenze.
0x981201C2 ETC_DCM_E_MAX_CTL_ERROR_EXCEED Controller error: Synchronisation beyond the limits
Internal error. Please contact Lenze.
0x981201C3 ETC_DCM_E_NOMEMORY Not enough memory location available.
Internal error. Please contact Lenze.
0x981201C4 ETC_DCM_E_INVALID_HWLAYER Hardware error: Invalid (BSP)
Internal error. Please contact Lenze.
0x981201C5 ETC_DCM_E_TIMER_MODIFY_ERROR Hardware error: Error at timer change
Internal error. Please contact Lenze.
0x981201C6 ETC_DCM_E_TIMER_NOT_RUNNING Hardware error: The timer does not run.
Internal error. Please contact Lenze.
0x981201C7 ETC_DCM_E_WRONG_CPU Hardware error: The function has been called on the wrong CPU.
Internal error. Please contact Lenze.
0x981201C8 ETC_DCM_E_INVALID_SYNC_
PERIOD
Invalid DC-Sync. Period length (invalid DC-master?)
Internal error. Please contact Lenze.
0x981201C9 ETC_DCM_E_INVALID_SETVAL DCM controller error: The set value is too low.
Internal error. Please contact Lenze.
0x981201CA ETC_DCM_E_DRIFT_TO_HIGH DCM controller error: The deviation between the local timer and the reference
clock is too high.
Internal error. Please contact Lenze.
0x98110181 ETC_EMRAS_E_INVALIDCOOKIE Reconnecting using the old cookie has failed. A new reconnection attempt is
made automatically.
Internal error. Please contact Lenze.
Error no.
[hex]
Designation Description