7 Commissioning of the system
7.3 Detailed description of the commissioning steps
48
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C. Store the parameters of the Servo-Inverter i700 in a non-volatile memory so that they are
retained in the device when the power is switched off:
In the boot project of the Lenze Controller, there is a separate parameter set for the lower-level
Servo-Inverters i700. The latter is then only updated when the "boot project" function is
executed via the »PLC Designer«. The current parameterisation is then saved and is available
after mains switching. During boot-up after mains connection, the saved parameter set is
automatically written from the controller into the servo inverter.
[7-2] Parameter set transfer from the 3231 C controller to the Servo-Inverter i700 during a boot-up