9 Mains and environment
9.2 Ambient conditions
278
Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Unearthed power systems
IT systems are power systems with an isolated neutral. They are used in the following countries and
industry sectors:
In the public supply system in France and Belgium
•Chemical industry
•Mining
Island power supplies (own generator)
•Hospitals
•Ship's mains
Crane, conveyor, and hoist systems
Paper and pulp industry
Advantages of the IT systems are the high fire and operator safety. Furthermore there is no discon-
nection during the first earth fault.
9.2 Ambient conditions
9.2.1 Max. ambient temperature, motor/gearbox
The permissible load capacity depends on the ambient temperature. The load capacity also depends
on whether a geared motor or a motor without a gearbox is used.
Tip!
If a geared motor is used, the derating starts from a temperature of 30 °C, in the case of a
motor without a gearbox it starts from 40 °C.
Depending on the site altitude, the following correction values k
ϑ
result for geared motors:
ϑ
opr
k
ϑ
1000 m 2000 m 3000 m 4000 m
20 °C 1.15 1.04 0.92 0.81
30 °C 1 0.9 0.8 0.70
40 °C 0.8 0.72 0.64 0.56
50 °C 0.6 0.54 0.48 0.42
60 °C 0.4 0.36 0.32 0.28