MODEL
NUMBER
(NOTE 1)
FOR MOTORS
RATED
INPUT (50-60 Hz) OUTPUT
HEAT LOSS
(WATTS)
(NOTE 5)
INPUT
PHASE
CURRENT
(AMPS)
POWER
(kVA)
CURRENT
(AMPS)
HP kW
TF400 SERIES (NOTE 3) 400 / 480 Vac 0 - 400 / 460 Vac
TF405 0.5 0.37 3 1.6 / 1.4 1.1 1.3 / 1.1 26
TF410 1 0.75 3 2.9 / 2.5 2.1 2.4 / 2.1 40
TF415 1.5 1.1 3 4.0 / 3.6 3.0 3.4 / 3.0 56
TF420 2 1.5 3 4.6 / 4.0 3.3 3.9 / 3.4 67
TF430 3 2.2 3 6.2 / 5.4 4.5 5.5 / 4.8 100
TF450 5 4.0 3 10.6 / 8.8 7.1 9.4 / 7.8 168
TF475 7.5 5.5 3 14.2 / 12.4 10.3 12.6 / 11.0 254
TF4100 10 7.5 3 18.1 / 15.8 13.1 16.1 / 14.0 310
TF500 SERIES (NOTE 4) 480 / 590 Vac 0 - 460 / 575 Vac
TF510 1 0.75 3 2.2 / 2.0 1.9 / 2.0 1.9 / 1.7 40
TF520 2 1.5 3 4.0 / 3.5 3.3 / 3.6 3.4 / 3.0 67
TF530 3 2.2 3 4.7 / 4.7 3.9 / 4.8 4.2 / 4.2 100
TF550 5 3.7 3 7.4 / 7.4 6.1 / 7.5 6.6 / 6.6 168
TF575 7.5 5.5 3 11.2 / 11.2 9.3 / 11.4 9.9 / 9.9 254
TF5100 10 7.5 3 13.7 / 13.7 11.4 / 14.0 12.2 / 12.2 310
NOTE 1: Refer to Section 3 for model number breakdown.
NOTE 3: The higher current ratings are for 400 Vac input and the lower current ratings are for 480 Vac input.
NOTE 4: The higher current ratings are for 480 Vac input and the lower current ratings are for 590 Vac input.
NOTE 5: Values are worst-case (not typical) for 4kHz carrier frequency at full speed and full load
8