7 INPUT AC POWER REQUIREMENTS
DANGER!
Hazard of electrical shock! Capacitors retain charge after they've been
removed. Disconnect incoming power and wait until the voltage between
terminals B+ and B- is 0 VDC before servicing the drive.
The input voltage must match the nameplate voltage rating of the drive. Voltage fluctuation
must not vary by greater than 10% over voltage or 15% under voltage.
NOTE
Drives with dual input voltage ratings must be programmed for the proper
supply voltage (refer to Parameter 01 - LINE VOLTAGE SELECTION in
Section 15 - DESCRIPTION OF PARAMETERS).
The drive is suitable for use on a circuit capable of delivering not more than 5,000 RMS
symmetrical amperes at 5 HP (4.0 kW) and below, and 18,000 RMS symmetrical amperes at
7.5 - 10 HP (5.5 - 7.5 kW), at the drive’s rated voltage.
If the kVA rating of the AC supply transformer is greater than 10 times the input kVA rating
of the drive(s), an isolation transformer or 2-3% input line reactor must be added to the line
side of the drive(s).
Three phase voltage imbalance must be less than 2.0% phase to phase. Excessive phase to
phase imbalance can cause severe damage to the drive’s power components.
Motor voltage should match line voltage in normal applications. The drive’s maximum output
voltage will equal the input voltage. Use extreme caution when using a motor with a voltage
rating which is different from the input line voltage.
7.1 INPUT VOLTAGE RATINGS
TF200 Series drives are rated for 208/240 Vac, three phase, 50-60 Hz input. The drive will
function with input voltages of 208 to 240 Vac (+10%, -15%) at 48 to 62 Hz.
TF200Y Series drives are rated for 208/240 Vac, single or three phase, 50-60 Hz input. The
drive will function with input voltage of 208 to 240 Vac (+10%, -15%) at 48 to 62 Hz.
TF400 Series drives are rated for 400/480 Vac three phase, 50-60 Hz input. The drive will
function with input voltages of 400 to 480 Vac (+10%, -15%) at 48 to 62 Hz.
TF500 Series drives are rated for 480/590 Vac, three phase, 50-60 Hz input, and will function
with input voltages of 480 to 590 Vac (+10%, -15%) at 48 to 62 Hz.
NOTE
Parameter 01 - LINE VOLTAGE SELECTION must be programmed
according to the applied input voltage. Refer to Section 15 - DESCRIPTION
OF PARAMETERS.