11.6 BIPOLAR SPEED CONTRO L (-10 to +10 VDC)
The three wiring diagrams herein provide examples of using a -10 to +10 VDC bipolar speed
reference.
SIGNAL COMMON
0-10 VDC INPUT
1 2
5 6
11
-10 to +10 VDC
SOURCE
(such as PLC)
SIGNAL COMMON
0-10 VDC INPUT
1 2
5 6
11
10V10V
SPEED POT
(2.5k - 10 k)
-
+
-
+
SIGNAL COMMON
0-10 VDC INPUT
1 2
5 6
11
+10 VDC SUPPLY
10V
SPEED POT
(2.5k - 10 k)
-
+
(COM) (SIGNAL)
NOTES:
To use a -10 to +10 VDC speed reference signal, the following parameters
must be set:
P07 BIPOLAR REFERENCE SELECTION must be set to ENABLE (02).
P17 ROTATION must be set to FORWARD AND REVERSE (02).
P45 SPEED AT MIN SIGNAL must be set to the maximum desired
speed in the reverse direction.
P46 SPEED AT MAX SIGNAL must be set to the maximum desired
speed in the forward direction.
In this configuration, all other speed references are disabled except JOG
FORWARD and JOG REVERSE.
In this configuration, the RUN and START functions on TB-13A and
TB-13D will only start the drive, they will not select direction. Direction is
determined by the polarity of the -10 to +10 VDC signal.