13.2 TCF DRIVE PERSONALITY
Each TCF model has a unique "personality" (voltage and HP). This information is stored in
the EPM, and is also permanently stored within the drive. If the EPM is replaced, and the
personality stored in the EPM does not match the personality stored in the drive, it may trip
into a "bF" fault, depending on the information stored on the new EPM.
1. If the new EPM was from a TCF drive that was configured for V/Hz mode (refer to
Parameter 80 - DRIVE MODE), the drive will operate normally and will not trip into a "bF"
fault. To set up the drive for Vector mode, follow the instructions in Appendix A.
2. If the new EPM was from a TCF drive that was configured for Vector mode or
Enhanced V/Hz mode (refer to Parameter 80 - DRIVE MODE), the drive will trip into a
"bF" fault. This fault can be reset by one of two methods:
a. Perform a RESET 60 or RESET 50 using Parameter 48 - PROGRAM
SELECTION. This will reset all of the parameters back to factory defaults. To
set up the drive for Vector or Enhanced V/Hz mode, follow the instructions in
Appendix A.
b. Set parameters 85-91 properly for the connected motor and then set Parameter
94 - DRIVE PERSONALITY to the correct value based on the HP and voltage
rating of the drive. Then perform the Auto Calibration function according to the
instructions in Appendix A.
NOTE
If an attempt is made to change Parameter 94 - DRIVE PERSONALITY
before parameters 85-91 are changed, the drive will display a "GH" fault.