11.4 THREE-WIRE START/STOP CONTROL
This wiring diagram shows a typical three-wire start/stop control scheme, using momentary
contacts (such as push-buttons) for START and STOP commands, and a selector switch to
select rotation direction.
MOMENTARY
STOP CONTACT
SIGNAL COMMON
0-10 VDC INPUT
DIGITAL INPUT REFERENCE
START
4-20 mA INPUT
1 2
5 6
14
TXA TXB
4 13A 13B 13C4 13D 2511 15 30
2
SIGNAL COMMON
(See Note 3)
START FORWARD
MOMENTARY
START CONTACT
(See Note 3)
FWDREV
START REVERSE
NOTES
• Momentarily close TB-13A or TB-13D to TB-4 to START the drive in the
desired direction and momentarily open TB-1 to TB-4 to STOP the drive.
• For this configuration, ROTATION DIRECTION (Parameter 17) must be
set to FORWARD AND REVERSE (02), TB-13A (Parameter 10) must be
set to START REVERSE (07), and TB-13D (Parameter 49) must be set to
START FORWARD (05).
If reverse direction is not required, wire the START push-button
directly between TB-4 and TB-13D, and do not program TB-13A for
START REVERSE.
• For 0-10 VDC or 4-20 mA speed control, use one of the following methods:
- Program Parameter 05 - STANDARD REFERENCE SOURCE for
0-10 VDC (03) or 4-20 mA (04). This method is preferable if only one
speed source is required, as this method leaves the TB-13 terminals
free to be used for other functions.
- Program one of the TB-13 terminals (13B or 13C are available in
this example) for 0-10 VDC (02) or 4-20 mA (03). When that TB-13
terminal is closed to TB-4, the drive will respond to the selected
speed reference signal. If that TB-13 terminal is not closed to TB-
4, the drive will respond to the speed control source selected in
Parameter 05 - STANDARD REFERENCE SOURCE.
23