9 TCF POWER WIRING DIAGRAM
THREE PHASE INPUT
(ALL SERIES)
L1 L2 L3
OUTPUT (ALL SERIES)
3 PHASE
AC MOTOR
DC BUS
VOLTAGE
T1 T2 T3 B- B+
+
SINGLE PHASE INPUT
(TF200Y SERIES)
L1 L2 L3
For all other models,
use output torque values.
TF230Y &
TF250 only
7.0 lb-in / 0.8 Nm
0.24 in / 6 mm
0.5 - 5 HP
(0.37 - 3.7 kW)
4.5 lb-in / 0.5 Nm
0.24 in / 6 mm
7.5 - 10 HP
(5.5 - 7.5 kW)
10 lb-in / 1.2 Nm
0.35 in / 9 mm
STOP!
• Do NOT connect AC line power to output terminals T1, T2, or T3. Severe
damage to the drive will result.
• Leakage current may exceed 3.5 mA AC. Minimum size of the protective
earth conductor shall comply with local safety regulations for high leakage
current equipment.
• Wire and Ground in accordance with NEC or CEC, and all applicable
local codes.
• Motor wires MUST be run in a separate steel conduit away from control
wiring and incoming AC power wiring.
• Do not install contactors between the drive and the motor without
consulting Lenze-AC Tech for more information. Failure to do so may
result in drive damage.
• Use only UL and CSA listed and approved wire.
• Minimum wire voltage rating is 300 V for 120, 208, and 240 Vac systems,
and 600 V for 400 and 480 Vac systems.
• Wire gauge must be based on a minimum of 125% of the rated input/
output current of the drive, and a minimum 75°C insulation rating. Use
copper wire only.