P44 PASSWORD
This allows the PASSWORD to be changed to any number between 000 and 999. Setting
PASSWORD to 000 disables the password function.
NOTE
The factory default password is 225.
P45 SPEED AT MIN SIGNAL
This sets the speed at which the drive will run when it receives the minimum speed reference
signal (0 VDC or 4 mA). This is used in conjunction with SPEED AT MAX SIGNAL (Parameter
46) to define the speed range of the drive when following an analog speed reference signal.
NOTE
When the drive is configured for -10 to +10 VDC speed control, SPEED AT
MIN SIGNAL will set the maximum speed that the drive will run at in reverse
direction when it receives -10 VDC. Refer to Parameter 07 - BIPOLAR
REFERENCE SELECTION.
P46 SPEED AT MAX SIGNAL
This sets the speed at which the drive will run when it receives the maximum speed reference
signal (10 VDC or 20 mA). This is used in conjunction with SPEED AT MIN SIGNAL (Parameter
45) to define the speed range of the drive when following an analog speed reference signal.
NOTE
If SPEED AT MIN SIGNAL is set higher than SPEED AT MAX SIGNAL, the
drive will react inversely to the speed reference signal. Therefore, as the speed
reference signal increases, the drive speed will decrease, and vice-versa. This
function is disabled when using a -10 to +10 VDC speed reference signal. Refer
to Parameter 07 - BIPOLAR REFERENCE SELECTION.
P47 CLEAR FAULT HISTORY
01 MAINTAIN: Maintains the FAULT HISTORY (Parameter 50) entries for
troubleshooting.
02 CLEAR: Erases the FAULT HISTORY (Parameter 50) entries.