P13 TB-15 OPEN COLLECTOR OUTPUT
This selects the status indication for the open-collector output at TB-15, and has the same
selections as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT.
P14 CONTROL
This selects the source of START/STOP and direction commands.
01 TERMINAL STRIP ONLY: The drive will only respond to START/STOP and
direction commands from the terminal strip.
02 REMOTE KEYPAD ONLY: The drive will only respond to START/STOP and
direction commands from the optional remote keypad.
03 TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A, TB-13C, or
TB-13D can be used to select terminal strip control or remote keypad control.
Refer to Parameters 10, 12, and 49.
NOTE
The STOP button on the optional remote keypad is always active as long as
the serial link remains intact.
P15 SERIAL LINK
This parameter configures the drive for Modbus RTU serial communications. The options are
listed by baud rate, number of data bits, parity, number of stop bits and whether the watchdog
timer is enabled or disabled.
WARNING!
Controlling the drive from the serial link without the watchdog timer could
cause damage to equipment and/or injury to personnel!
The watchdog timer will stop the drive after 10 seconds of no serial activity to safeguard
against a failed serial link. During set-up or troubleshooting it may be useful to disable the
watchdog timer but is it not recommended to run normally without the watchdog timer.
01 DISABLED: Disables the serial link
02 9600, 8, N, 2 - ENABLED WITH TIMER
03 9600, 8, N, 2 - ENABLED WITHOUT TIMER
04 9600, 8, E, 1 - ENABLED WITH TIMER
05 9600, 8, E, 1 - ENABLED WITHOUT TIMER
06 9600, 8, O, 1 - ENABLED WITH TIMER
07 9600, 8, O, 1 - ENABLED WITHOUT TIMER
43