05 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart
attempts are unsuccessful, or if input power is removed.
06 AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.
07 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds the value
in PRESET SPEED #3. Opens if the output frequency is equal to or less than
the value in PRESET SPEED #3 (Parameter 33).
08 CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT
setting. Opens if the output current is equal to or less than CURRENT LIMIT
(refer to Parameter 25).
09 AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed
reference is selected using TB-13A, 13B, 13C, or 13D. Opens if a STANDARD
(Parameter 5) speed reference is active.
10 REVERSE: Closes when reverse rotation is active. Opens when forward rotation
is active. (Refer to Parameter 17 - ROTATION DIRECTION).
11 DYNAMIC BRAKING: Used to "trigger" the optional external Dynamic Braking
module. Refer to the instructions included with the Dynamic Braking option.
P07 BIPOLAR REFERENCE SELECTION
This parameter is used to enable the -10 to +10 VDC bipolar speed reference input (cannot
be used as a torque reference). Refer to Section 11.6 for -10 to +10 VDC wiring examples.
01 DISABLE: The drive will operate normally and respond to the speed reference
selected in Parameter 5 - STANDARD REFERENCE SOURCE, or selected
using terminals 13A, 13B, 13C, and 13D. Refer to Section 10.6 for more
information on speed reference selection.
02 ENABLE: The drive will only respond to a -10 to +10 VDC bipolar signal (all
other speed references are disabled).
From +0.1 to +10 VDC the drive will operate in the Forward direction, with the
maximum speed determined by SPEED AT MAX SIGNAL (Parameter 46) or
MAXIMUM FREQUENCY (Parameter 24), whichever is lower.
From -0.1 to -10 VDC, the drive will operate in the Reverse direction, with the
maximum speed determined by SPEED AT MIN SIGNAL (Parameter 45) or
MAXIMUM FREQUENCY (Parameter 24), whichever is lower.
NOTE
• When setting 02 is selected, Parameter 17 - ROTATION must be set to
FORWARD AND REVERSE (02) for the bipolar speed reference to work
properly.
• When setting 02 is selected, the RUN and START functions on terminals
TB-13A and TB-13D can only be used to start the drive; they will no longer
select direction (direction is only determined by the polarity of the -10 to
+10 VDC signal). However, TB-13B and TB-13C can still be used for JOG
FORWARD and JOG REVERSE functions.
Refer to Parameters 10, 11, 12, and 49